Timeo Gate installation guide
Put the reader on your door in one visit. Members scan the pass in the Timeo app or tap their card, and the door releases while their membership is active.
01In the box
- Timeo Gate reader (black, 3.3-inch touchscreen), mounting bracket, two M4 screws, drilling template, plastic pry tool
- Reader wiring harness, 10 wires, labelled at the plug end
- Access-control power supply, 12 V 5 A, with
PUSHinput andNC/NOlock outputs. Mains input is two bare red leads. - Maglock, 280 kg, with bracket. Its two screw terminals, marked
+and−, are under the end cap of the magnet body. - Exit button, white 86 mm panel marked EXIT, normally open, two screw terminals on the back (no wire attached)
Your reader is already registered to your business before it ships. The serial number is printed on the back and shown on the reader's screen once it is powered.
02What you still need on install day
Three things, all from a hardware shop. Nothing else.
- One roll of 2-core 1.0 mm² flexible cable, for the magnet.Ask for "RVV 2×1.0". Runs from the power supply to the maglock. Buy the length of that run plus 2 m spare. About RM 2 to 3 per metre.
- One roll of 2-core 0.5 mm² flexible cable, for the reader and the exit button.Ask for "RVV 2×0.5". Two runs: power supply to the exit button, and power supply to the reader if the reader's own harness does not reach. Buy both runs plus 2 m spare. About RM 1 to 2 per metre.
- One 3-pin mains plug with a lead, for the power supply.The power supply's mains input is two bare red leads. Join them to a plug lead (any 3-pin plug with 1 m of flex, about RM 10) or have the electrician run it to a fused spur. Without this the power supply cannot be switched on.
Plus one network cable, Cat5e or better, from the router or switch to the reader. The reader connects by cable, not Wi-Fi. About RM 20 to 40.
Do not buy
- A power supply, magnet, exit button or reader. All four are in the box.
- A separate 12 V adapter. The supplied power supply powers the reader and the magnet together.
- A wall box. Optional only for a flush mount; the reader's bracket also screws straight onto the wall.
How many wire ends go into the power supply? Ten: four from the reader's harness, two from the magnet, two from the exit button, and the two red mains leads. Section 4 lists every one.
Using an electric strike instead of the supplied maglock? That works too if your door frame suits it. Use the power supply's NO output for a fail-secure strike and NC for a fail-safe one. Everything else in this guide stays the same.
03Where to mount it
The reader
- Outside the door, handle side, centre of the reader about 1.3 m from the floor.
- Out of direct sun and strong lamps. The scanner is a camera; glare on the glass stops it reading phone screens.
- Keep metal 10 cm away from the lower half of the glass. That is where the card antenna sits, and a steel frame right behind it shortens the tap range.
- Indoor or sheltered only. It is not rated for rain.
- Stick the drilling template on the wall, level.Drill the four M4 holes. If there is an 86 mm box in the wall, use its two screw holes instead. Drill a hole in the middle for the harness and the network cable.
- Screw the black bracket on.The arrow moulded into it points up. Mount it landscape (wide) unless we told you otherwise.
- Pass the harness and network cable through the bracket's centre openingand plug both into the back of the reader.
- Hook the reader onto the top clips and press the bottom until it snaps.To remove it later, slide the plastic pry tool into the top slot first, then the two at the bottom. Never a metal screwdriver; it marks the case and voids the warranty.
The exit button
Inside the door, handle side, about 1.2 m up, in an 86 mm box or on the surface. Two screw terminals on the back; the wiring is in section 4.
The maglock
- The magnet body goes on the door frame, the steel plate on the door, at the top corner on the opening side.
- Door opens inward: L bracket, magnet under the head of the frame.
- Door opens outward: Z bracket, which steps the plate out to meet the magnet.
- Fit the plate with its rubber washer and leave it a little loose. That play lets it seat flat against the magnet.
- Mount the magnet with the end cap that has the single screw facing the side your cable comes from. The wiring terminals are under that cap.
The power supply
Inside, out of reach, near the door: above a false ceiling or on the wall beside the frame. Two keyhole slots on the back take two screws. Keep it within cable reach of a socket; it takes a normal 3-pin plug.
04Wiring
For the electrician. Power off everything while connecting, and wait two seconds between switching the supply off and on again.
Harness wire colours
Printed on the tag tied to the harness. Listed here so nobody has to read a 4 mm label on a ladder.
| Pin | Colour | Signal | Use |
|---|---|---|---|
| 1 | Red | VCC (12V) | Used. To the power supply's DC12V |
| 2 | Black | GND | Used. To the power supply's GND beside DC12V |
| 3 | Green | INPUT (EXIT) | Not used, tape it |
| 4 | Grey | GND | Not used, tape it |
| 5 | Violet | NO | Used. To the power supply's PUSH |
| 6 | Yellow | 485-A | Not used, tape it |
| 7 | Blue | COM | Used. To the power supply's GND beside PUSH |
| 8 | Brown | 485-B | Not used, tape it |
| 9 | Orange | NC | Not used, tape it |
| 10 | White | SEN | Not used, tape it |
The power supply's terminals
The supplied unit is a 12 V 5 A access-control supply. Mains (90 to 260 V AC) goes to the two red leads at the top; they need a plug fitted or a fused spur. The green screw block reads, left to right:
| Terminal | What it is | Connect |
|---|---|---|
| NO | Lock output, powered only while unlocking | Nothing (used for a fail-secure strike) |
| GND | Lock output return | Maglock − |
| NC | Lock output, powered except while unlocking | Maglock + |
| DC12V | 12 V for the reader | Reader red (VCC) |
| GND | Return for the reader and the PUSH input | Reader black (GND), reader blue (COM), exit button second terminal |
| PUSH | Unlock input. Shorting it to GND unlocks | Reader violet (NO), exit button first terminal |
| +CONTROL / −CONTROL | Alternative unlock input for a separate controller | Nothing |
| Time | Unlock hold time adjuster (small screw) | Turn fully anticlockwise (shortest). The reader sets the hold. |
Inside the maglock
Undo the single screw on the end cap of the magnet body and slide the cap off. Inside is a small blue board with a green two-screw block marked + and −. Those two screws are the only connection you make to the magnet.
+(left screw) takes the wire from the power supply'sNC.−(right screw) takes the wire from the power supply'sGNDbesideNC.- The four thin wires (red, yellow, white, black) on the small white plug next to the block are the magnet's own coil connection. Leave that plug alone.
- There is no 12 V / 24 V jumper on this magnet. Feed it 12 V from the supplied power supply and nothing needs setting.
Get + and − the right way round. The board in the magnet is polarity sensitive. Wired backwards, the magnet holds weakly or not at all, and nothing is damaged, so swap the two wires and try again.
Connections
| From | To | Why |
|---|---|---|
| Reader red (12V) | Power supply DC12V | Powers the reader |
| Reader black (GND) | Power supply GND (beside DC12V) | |
| Reader violet (NO) | Power supply PUSH | The reader's relay acts exactly like an exit button. When Timeo says "open", the reader closes NO to COM for three seconds and the power supply drops the lock. |
| Reader blue (COM) | Power supply GND (beside PUSH) | The reader's relay acts exactly like an exit button. When Timeo says "open", the reader closes NO to COM for three seconds and the power supply drops the lock. |
| Exit button, both terminals | Power supply PUSH + GND | In parallel with the reader. The button is normally open; either way round. |
| Maglock + (green block, left) | Power supply NC | Powered means locked. Losing power opens the door. |
| Maglock − (green block, right) | Power supply GND (beside NO/NC) | Powered means locked. Losing power opens the door. |
| Router or switch | Reader network port | Any free LAN port |
Do not run the lock through the reader's own relay contacts. They are rated for 30 V / 1 A signalling, not for switching a maglock. Let the power supply switch the lock; the reader only tells it when.
Turn the power supply's Time screw fully anticlockwise, the shortest setting. The reader already holds the request for three seconds.
Cable runs: 2 × 1.0 mm² is good for power up to 100 m; 2 × 0.5 mm² for the relay and exit button up to 100 m.
If the installer was handed the maker's drawings
05Network
Plug the network cable in and the reader gets an address from your router by itself. Nothing to configure. It needs ordinary internet access to reach Timeo, the same as a laptop on your Wi-Fi.
- Two small lights on the network port show link (steady) and traffic (blinking).
- The footer of the screen shows the address it received, for example
192.168.0.42. The middle line reads Scan your pass or tap your card once it has spoken to Timeo. - If your router has a guest network or client isolation, put the reader on the main network.
06Connect it to your Timeo account
Done once, from any computer or phone signed in to your Timeo console.
Shipped ready? If we linked the reader to your account before sending it, there is nothing to do here: plug in the power and the network cable, and within a minute the screen shows your business name and Scan your pass or tap your card. Use the steps below only if the screen says Not set up.
- Power the reader and plug in the network cable.Wait until the screen shows the clock and the footer shows a network address.
- Open Timeo, go to Settings, then Hardware.Find the section named Timeo Gate readers.
- Add the reader.Give it a name such as "Front door", type the serial exactly as shown in the reader's footer, and choose Add reader. If it was registered for you before shipping, it is already listed.
- Show the setup code.A square code appears on your screen. Hold it 10 to 15 cm from the reader's glass, phone brightness up.
- Wait for the confirmation.The screen says "Set up for your business, restarting". Within a minute the top of the screen shows your business name and the middle line reads Scan your pass or tap your card.
The setup code only works on the reader whose serial it was made for. You can show it again any time from the same page, for example after moving the reader to a different door.
07Test the door
Power-on order: plug the power supply in, wait for the reader to show the clock, then:
- Press the exit button.The power supply clicks and the lock releases. This does not involve the reader at all, so it proves the lock wiring on its own.
- Scan an active member's pass.Open the Timeo app, show the pass, hold it to the glass. The screen turns green with the member's name, you hear two short beeps, and the lock releases for three seconds.
- Scan a lapsed member.Red screen, the member's name, and the reason, for example "No active package". One long beep. The door stays locked.
- Pull the reader's power for ten seconds and plug it back in.It comes back by itself and shows your business name within a minute. No one needs to touch it.
- Check the log.In Timeo, open Door logs. Every scan you just made is there with the time and the decision.
08Everyday use
Members show the pass from the Timeo app, or tap a card you registered on their profile. The pass in the app refreshes on its own and cannot be shared by screenshot.
Registering a card
- Tap the new card on the reader.It says "Card not recognised". That is expected: the reader has just told Timeo the card's number.
- Open the member in Timeo.Customers, then the member, then Reset NFC next to "NFC card". Works from a phone as well.
- Pick the card.Under Tapped on the gate reader the card you just tapped is listed with the time. Choose Use this card, then Save card.
- Tap again.The screen says Welcome with the member's name and the door releases.
Staff cards are registered the same way from Staff, then the person's profile. A card can belong to one person at a time; saving it on someone else moves it.
- A membership that runs out keeps working at the door for seven more days so people can renew at the counter. After that the reader turns them away and tells them why.
- Staff with a registered card enter regardless of membership.
- Every entry and every refusal is in Door logs, with the reason. Nothing is stored on the reader itself.
- Renewals and new sign-ups take effect at the door within seconds.
09What the screen is telling you
The reader speaks in short messages. Green means the door opened, red means it stayed shut, blue is about the reader itself.
Membership active, door released for three seconds.
The member's name is shown underneath.
Membership ended more than seven days ago, or none was ever bought.
Renew at the counter or in the app, then scan again.
The pass or card is not one Timeo issued for this business.
Open the Timeo app afresh. For a card, check it is registered on the member's profile.
The pass on the phone has expired. Passes refresh every 30 seconds.
Reopen the pass in the app and scan again.
This reader is set to admit staff only.
Members use the main entrance.
The reader could not reach Timeo just now.
See section 10. Let people in from the counter meanwhile.
Normal, ready.
No network address yet.
Check the cable and the router port. The top-right icon shows a red cross while the cable is out.
Network is up, first contact with Timeo pending. Normal for the first minute after power-on.
If it stays longer than two minutes, check your internet connection.
A scan could not reach Timeo just now.
Check your internet connection. Let people in from the counter meanwhile.
The reader is not linked to a business yet.
Follow section 6.
Setup code accepted, restarting.
The code was made for a different serial, or for a different business than the one this reader already belongs to.
Show the code from the Hardware page of the business that owns this reader.
The QR camera failed to open at power-on. The reader restarts itself once and normally comes back fine.
If it keeps showing this, power it off for ten seconds and on again.
Beeps: one short beep on every scan, two short beeps for open, one long beep for refused.
10If something is wrong
| You see | Check |
|---|---|
| Screen is dark | 12 V and GND at the reader plug. Power supply switched on. Wait two seconds between off and on. |
| Screen says "No network" | Cable clicked in at both ends. Port lights on the reader. Try another port on the router. |
| Footer shows an address but the screen stays on "Connecting to Timeo" | Your internet is down or blocked. Test on a phone on the same Wi-Fi. Guest networks and client isolation block the reader. |
| Green screen, beeps, but the door does not release | The reader is fine. Check NO to PUSH and COM to GND, and that the power supply's lock output is the one the maglock is on. Press the exit button: if that also fails, the fault is in the supply or lock wiring. |
| Door releases but only for an instant | Power supply unlock delay is doing the timing. Set it to minimum; the reader holds for three seconds. |
| Magnet never holds, or holds weakly, even with nothing pressed | Open the magnet's end cap and check + and − on the green block are the right way round (+ from NC, − from GND). Then check the plate sits flat on the magnet face; loosen the plate screw a little if it rocks. If both are right and it still holds weakly, measure resistance across + and − with the power off: about 25 to 35 Ω is a 12 V coil and is fine; about 100 Ω is a 24 V coil, so stop and contact Timeo support. |
| Phone passes are slow to read or fail | Glare on the glass, or phone brightness low. Move the reader out of direct light; ask members to raise brightness. |
| Cards read only when touching the glass | Metal behind or beside the lower half of the reader. Add a spacer or move it 10 cm from the frame. |
| Reader shows a different business name | It was set up under another account. Show the setup code from your own Hardware page and scan it. |
| Reader stuck on the vendor start screen after power on | Contact Timeo support with the serial. Do not attempt to reset it. |
When the reader cannot reach Timeo, it does not guess. The door stays locked and staff let members in from the counter. Nothing is lost: once it is back online, scans resume and are logged as normal.
11Specifications
- Reads
- QR pass from the Timeo app, Apple Wallet and Google Wallet passes, 13.56 MHz cards (ISO 14443A, Mifare)
- Screen
- 3.3-inch colour touchscreen, 320 × 480
- Power
- 12 V DC (9 to 15 V), 0.3 A, about 3.5 W
- Door output
- Dry-contact relay NO/COM/NC, rated 30 V / 1 A, signal only
- Network
- Ethernet 10/100, DHCP, outbound HTTPS to Timeo only
- Mounting
- Surface bracket or 86 mm wall box, landscape or portrait
- Environment
- Indoor, −20 to 60 °C
- Security
- Passes are encrypted and expire every 60 seconds. Access decisions are made by Timeo, not stored on the reader.
Support
Email hello@timeo.my with your business name, the reader's serial from the footer, and what the screen shows. We can see the reader's status and door logs from our side.